Mitsubishi Electric SUZ-SHWM60VAH(-SC)
Mitsubishi Electric · Ecodan Zubadan · pompa ciepła powietrze-woda · dane techniczne (datklima — bez cen)
Specyfikacja
- Źródło / typ
- air · split
- Czynnik chłodniczy
- R32
- Maks. temp. zasilania
- 60 °C
- Min. temp. powietrza
- -25 °C
- Temp. graniczna pracy (TOL)
- -25 °C
Wydajność grzewcza — zasilanie 25 °C
Moc grzewcza i COP wg temperatury powietrza zewnętrznego.
| Temp. powietrza | -10°C | -10°C | -10°C | -10°C | -7°C | -7°C | -7°C | -7°C | 2°C | 2°C | 2°C | 2°C | 7°C | 7°C | 7°C | 7°C | 12°C | 12°C | 12°C | 12°C | 15°C | 15°C | 15°C | 15°C | 20°C | 20°C | 20°C | 20°C |
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| Moc grzewcza | 4.80 kW | 5.00 kW | 6.00 kW | 8.20 kW | 4.30 kW | 4.80 kW | 6.00 kW | 8.20 kW | 4.10 kW | 4.80 kW | 6.00 kW | 7.80 kW | 3.80 kW | 4.00 kW | 5.00 kW | 8.90 kW | 3.60 kW | 4.80 kW | 6.00 kW | 8.90 kW | 4.00 kW | 4.80 kW | 6.00 kW | 9.70 kW | 4.70 kW | 4.80 kW | 6.00 kW | 11.10 kW |
| Pobór | 1.51 kW | 1.50 kW | 1.99 kW | 3.05 kW | 1.16 kW | 1.30 kW | 1.65 kW | 2.60 kW | 0.79 kW | 1.06 kW | 1.37 kW | 2.09 kW | 0.60 kW | 0.63 kW | 0.79 kW | 1.80 kW | 0.47 kW | 0.64 kW | 0.82 kW | 1.42 kW | 0.46 kW | 0.56 kW | 0.72 kW | 1.42 kW | 0.47 kW | 0.47 kW | 0.60 kW | 1.49 kW |
| COP | 3.18 | 3.33 | 3.01 | 2.69 | 3.70 | 3.68 | 3.64 | 3.16 | 5.22 | 4.51 | 4.38 | 3.74 | 6.33 | 6.32 | 6.31 | 4.93 | 7.58 | 7.51 | 7.29 | 6.25 | 8.69 | 8.57 | 8.34 | 6.85 | 10.02 | 10.18 | 9.97 | 7.47 |
Proweniencja jednostki: dokument: ME Ecodan ATW databook v6.
Wydajność grzewcza — zasilanie 35 °C
Moc grzewcza i COP wg temperatury powietrza zewnętrznego.
| Temp. powietrza | -25°C | -25°C | -25°C | -25°C | -20°C | -20°C | -20°C | -20°C | -15°C | -15°C | -15°C | -15°C | -10°C | -10°C | -10°C | -10°C | -7°C | -7°C | -7°C | -7°C | 2°C | 2°C | 2°C | 2°C | 7°C | 7°C | 7°C | 7°C | 12°C | 12°C | 12°C | 12°C | 15°C | 15°C | 15°C | 15°C | 20°C | 20°C | 20°C | 20°C |
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| Moc grzewcza | 3.80 kW | 3.80 kW | 4.80 kW | 4.80 kW | 3.90 kW | 4.80 kW | 6.00 kW | 6.00 kW | 4.20 kW | 4.80 kW | 6.00 kW | 6.60 kW | 4.50 kW | 4.80 kW | 6.00 kW | 7.60 kW | 3.90 kW | 4.80 kW | 6.00 kW | 7.60 kW | 3.80 kW | 4.80 kW | 6.00 kW | 7.40 kW | 3.60 kW | 4.00 kW | 5.00 kW | 8.60 kW | 3.40 kW | 4.80 kW | 6.00 kW | 8.50 kW | 3.80 kW | 4.80 kW | 6.00 kW | 9.30 kW | 4.40 kW | 4.80 kW | 6.00 kW | 10.70 kW |
| Pobór | 2.36 kW | 2.36 kW | 2.77 kW | 2.77 kW | 1.49 kW | 2.58 kW | 3.21 kW | 3.21 kW | 1.58 kW | 2.19 kW | 2.87 kW | 3.22 kW | 1.69 kW | 1.91 kW | 2.52 kW | 3.50 kW | 1.32 kW | 1.63 kW | 2.09 kW | 2.95 kW | 0.91 kW | 1.31 kW | 1.73 kW | 2.36 kW | 0.72 kW | 0.81 kW | 1.01 kW | 2.13 kW | 0.58 kW | 0.82 kW | 1.05 kW | 1.69 kW | 0.57 kW | 0.72 kW | 0.92 kW | 1.69 kW | 0.53 kW | 0.59 kW | 0.75 kW | 1.71 kW |
| COP | 1.61 | 1.61 | 1.73 | 1.73 | 2.61 | 1.86 | 1.87 | 1.87 | 2.66 | 2.19 | 2.09 | 2.05 | 2.66 | 2.52 | 2.38 | 2.17 | 2.95 | 2.95 | 2.87 | 2.58 | 4.17 | 3.65 | 3.47 | 3.13 | 4.98 | 4.96 | 4.95 | 4.04 | 5.84 | 5.88 | 5.73 | 5.04 | 6.61 | 6.63 | 6.49 | 5.50 | 8.28 | 8.10 | 7.98 | 6.27 |
Proweniencja jednostki: dokument: ME Ecodan ATW databook v6.
Wydajność grzewcza — zasilanie 40 °C
Moc grzewcza i COP wg temperatury powietrza zewnętrznego.
| Temp. powietrza | -25°C | -25°C | -25°C | -25°C | -20°C | -20°C | -20°C | -20°C | -15°C | -15°C | -15°C | -15°C | -10°C | -10°C | -10°C | -10°C | -7°C | -7°C | -7°C | -7°C | 2°C | 2°C | 2°C | 2°C | 7°C | 7°C | 7°C | 7°C | 12°C | 12°C | 12°C | 12°C | 15°C | 15°C | 15°C | 15°C | 20°C | 20°C | 20°C | 20°C |
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| Moc grzewcza | 3.60 kW | 3.60 kW | 4.40 kW | 4.40 kW | 3.60 kW | 4.50 kW | 5.60 kW | 5.60 kW | 3.80 kW | 4.80 kW | 6.00 kW | 6.60 kW | 4.30 kW | 4.80 kW | 6.00 kW | 7.30 kW | 3.70 kW | 4.80 kW | 6.00 kW | 7.30 kW | 3.70 kW | 4.80 kW | 6.00 kW | 7.20 kW | 3.50 kW | 4.00 kW | 5.00 kW | 8.50 kW | 3.30 kW | 4.80 kW | 6.00 kW | 8.30 kW | 3.70 kW | 4.80 kW | 6.00 kW | 9.10 kW | 4.30 kW | 4.80 kW | 6.00 kW | 10.50 kW |
| Pobór | 2.47 kW | 2.47 kW | 2.80 kW | 2.80 kW | 1.64 kW | 2.87 kW | 3.22 kW | 3.22 kW | 1.66 kW | 2.57 kW | 3.37 kW | 3.35 kW | 1.84 kW | 2.19 kW | 2.90 kW | 3.82 kW | 1.43 kW | 1.85 kW | 2.41 kW | 3.19 kW | 1.01 kW | 1.49 kW | 1.99 kW | 2.54 kW | 0.81 kW | 0.94 kW | 1.17 kW | 2.36 kW | 0.66 kW | 0.95 kW | 1.21 kW | 1.87 kW | 0.66 kW | 0.85 kW | 1.08 kW | 1.88 kW | 0.63 kW | 0.71 kW | 0.89 kW | 1.92 kW |
| COP | 1.46 | 1.46 | 1.57 | 1.57 | 2.19 | 1.57 | 1.74 | 1.74 | 2.29 | 1.87 | 1.78 | 1.97 | 2.33 | 2.19 | 2.07 | 1.91 | 2.58 | 2.59 | 2.49 | 2.29 | 3.65 | 3.22 | 3.01 | 2.83 | 4.31 | 4.28 | 4.27 | 3.60 | 4.97 | 5.07 | 4.95 | 4.44 | 5.57 | 5.66 | 5.57 | 4.83 | 6.86 | 6.79 | 6.73 | 5.48 |
Proweniencja jednostki: dokument: ME Ecodan ATW databook v6.
Wydajność grzewcza — zasilanie 45 °C
Moc grzewcza i COP wg temperatury powietrza zewnętrznego.
| Temp. powietrza | -20°C | -20°C | -20°C | -20°C | -15°C | -15°C | -15°C | -15°C | -10°C | -10°C | -10°C | -10°C | -7°C | -7°C | -7°C | -7°C | 2°C | 2°C | 2°C | 2°C | 7°C | 7°C | 7°C | 7°C | 12°C | 12°C | 12°C | 12°C | 15°C | 15°C | 15°C | 15°C | 20°C | 20°C | 20°C | 20°C |
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| Moc grzewcza | 3.30 kW | 4.20 kW | 5.20 kW | 5.20 kW | 3.40 kW | 4.60 kW | 5.70 kW | 5.70 kW | 4.00 kW | 4.80 kW | 6.00 kW | 7.00 kW | 3.50 kW | 4.80 kW | 6.00 kW | 7.00 kW | 3.50 kW | 4.80 kW | 6.00 kW | 7.00 kW | 3.40 kW | 4.00 kW | 5.00 kW | 8.30 kW | 3.20 kW | 4.80 kW | 6.00 kW | 8.10 kW | 3.60 kW | 4.80 kW | 6.00 kW | 8.90 kW | 4.10 kW | 4.80 kW | 6.00 kW | 10.30 kW |
| Pobór | 1.85 kW | 3.28 kW | 3.82 kW | 3.23 kW | 1.78 kW | 2.99 kW | 3.88 kW | 3.88 kW | 2.01 kW | 2.58 kW | 3.43 kW | 4.24 kW | 1.59 kW | 2.16 kW | 2.86 kW | 3.50 kW | 1.12 kW | 1.72 kW | 2.34 kW | 2.78 kW | 0.94 kW | 1.11 kW | 1.39 kW | 2.63 kW | 0.78 kW | 1.13 kW | 1.44 kW | 2.12 kW | 0.80 kW | 1.02 kW | 1.29 kW | 2.15 kW | 0.76 kW | 0.88 kW | 1.10 kW | 2.20 kW |
| COP | 1.78 | 1.28 | 1.36 | 1.61 | 1.91 | 1.54 | 1.47 | 1.47 | 1.99 | 1.86 | 1.75 | 1.65 | 2.20 | 2.22 | 2.10 | 2.00 | 3.12 | 2.79 | 2.56 | 2.52 | 3.63 | 3.60 | 3.59 | 3.15 | 4.10 | 4.25 | 4.17 | 3.83 | 4.53 | 4.69 | 4.64 | 4.15 | 5.43 | 5.48 | 5.47 | 4.68 |
Proweniencja jednostki: dokument: ME Ecodan ATW databook v6.
Wydajność grzewcza — zasilanie 50 °C
Moc grzewcza i COP wg temperatury powietrza zewnętrznego.
| Temp. powietrza | -15°C | -15°C | -15°C | -15°C | -10°C | -10°C | -10°C | -10°C | -7°C | -7°C | -7°C | -7°C | 2°C | 2°C | 2°C | 2°C | 7°C | 7°C | 7°C | 7°C | 12°C | 12°C | 12°C | 12°C | 15°C | 15°C | 15°C | 15°C | 20°C | 20°C | 20°C | 20°C |
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| Moc grzewcza | 3.00 kW | 4.20 kW | 5.30 kW | 5.30 kW | 3.90 kW | 4.70 kW | 5.90 kW | 6.40 kW | 3.50 kW | 4.80 kW | 6.00 kW | 6.60 kW | 3.40 kW | 4.80 kW | 6.00 kW | 6.50 kW | 3.40 kW | 4.00 kW | 5.00 kW | 7.50 kW | 3.20 kW | 4.80 kW | 6.00 kW | 7.40 kW | 3.50 kW | 4.80 kW | 6.00 kW | 7.80 kW | 4.00 kW | 4.80 kW | 6.00 kW | 8.50 kW |
| Pobór | 1.95 kW | 3.44 kW | 3.93 kW | 3.93 kW | 2.15 kW | 2.80 kW | 3.69 kW | 4.13 kW | 1.76 kW | 2.40 kW | 3.26 kW | 3.59 kW | 1.20 kW | 1.91 kW | 2.64 kW | 2.86 kW | 1.04 kW | 1.22 kW | 1.53 kW | 2.59 kW | 0.87 kW | 1.27 kW | 1.63 kW | 2.13 kW | 0.87 kW | 1.16 kW | 1.47 kW | 2.06 kW | 0.84 kW | 1.00 kW | 1.26 kW | 1.97 kW |
| COP | 1.54 | 1.22 | 1.35 | 1.35 | 1.81 | 1.68 | 1.60 | 1.55 | 1.99 | 2.00 | 1.84 | 1.84 | 2.83 | 2.51 | 2.27 | 2.27 | 3.28 | 3.28 | 3.27 | 2.90 | 3.67 | 3.78 | 3.68 | 3.47 | 4.03 | 4.14 | 4.08 | 3.79 | 4.77 | 4.79 | 4.76 | 4.32 |
Proweniencja jednostki: dokument: ME Ecodan ATW databook v6.
Wydajność grzewcza — zasilanie 55 °C
Moc grzewcza i COP wg temperatury powietrza zewnętrznego.
| Temp. powietrza | -15°C | -15°C | -15°C | -15°C | -10°C | -10°C | -10°C | -10°C | -7°C | -7°C | -7°C | -7°C | 2°C | 2°C | 2°C | 2°C | 7°C | 7°C | 7°C | 7°C | 12°C | 12°C | 12°C | 12°C | 15°C | 15°C | 15°C | 15°C | 20°C | 20°C | 20°C | 20°C |
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| Moc grzewcza | 3.20 kW | 3.80 kW | 4.80 kW | 4.80 kW | 3.80 kW | 4.60 kW | 5.70 kW | 5.70 kW | 3.40 kW | 4.80 kW | 6.00 kW | 6.10 kW | 3.30 kW | 4.80 kW | 6.00 kW | 6.00 kW | 3.30 kW | 4.00 kW | 5.00 kW | 6.70 kW | 3.10 kW | 4.80 kW | 6.00 kW | 6.70 kW | 3.40 kW | 4.80 kW | 6.00 kW | 6.70 kW | 3.90 kW | 4.80 kW | 6.00 kW | 6.70 kW |
| Pobór | 2.08 kW | 2.97 kW | 3.90 kW | 3.90 kW | 2.35 kW | 3.09 kW | 3.96 kW | 3.96 kW | 1.91 kW | 2.70 kW | 3.55 kW | 3.63 kW | 1.30 kW | 2.15 kW | 2.97 kW | 2.75 kW | 1.13 kW | 1.36 kW | 1.70 kW | 2.54 kW | 0.96 kW | 1.46 kW | 1.88 kW | 2.15 kW | 0.96 kW | 1.34 kW | 1.71 kW | 1.96 kW | 0.95 kW | 1.17 kW | 1.49 kW | 1.70 kW |
| COP | 1.54 | 1.28 | 1.23 | 1.23 | 1.62 | 1.49 | 1.44 | 1.44 | 1.78 | 1.78 | 1.69 | 1.68 | 2.54 | 2.23 | 2.02 | 2.18 | 2.93 | 2.95 | 2.94 | 2.64 | 3.24 | 3.30 | 3.19 | 3.11 | 3.53 | 3.59 | 3.51 | 3.42 | 4.10 | 4.09 | 4.04 | 3.95 |
Proweniencja jednostki: dokument: ME Ecodan ATW databook v6.
Wydajność grzewcza — zasilanie 60 °C
Moc grzewcza i COP wg temperatury powietrza zewnętrznego.
| Temp. powietrza | 2°C | 2°C | 2°C | 2°C | 7°C | 7°C | 7°C | 7°C | 12°C | 12°C | 12°C | 12°C | 15°C | 15°C | 15°C | 15°C | 20°C | 20°C | 20°C | 20°C |
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| Moc grzewcza | 3.20 kW | 4.00 kW | 5.00 kW | 5.00 kW | 3.30 kW | 3.80 kW | 4.80 kW | 4.80 kW | 3.10 kW | 3.80 kW | 4.80 kW | 4.80 kW | 3.30 kW | 3.80 kW | 4.80 kW | 4.80 kW | 3.80 kW | 3.80 kW | 4.80 kW | 4.80 kW |
| Pobór | 1.42 kW | 2.05 kW | 2.81 kW | 2.81 kW | 1.28 kW | 1.45 kW | 2.01 kW | 2.01 kW | 1.10 kW | 1.34 kW | 1.75 kW | 1.75 kW | 1.09 kW | 1.25 kW | 1.57 kW | 1.57 kW | 1.10 kW | 1.12 kW | 1.34 kW | 1.34 kW |
| COP | 2.25 | 1.95 | 1.78 | 1.78 | 2.58 | 2.63 | 2.39 | 2.39 | 2.81 | 2.83 | 2.75 | 2.75 | 3.03 | 3.04 | 3.06 | 3.06 | 3.44 | 3.40 | 3.59 | 3.59 |
Proweniencja jednostki: dokument: ME Ecodan ATW databook v6.
Źródło danych
Proweniencja jednostki: dokument: ME Ecodan ATW databook v6.
Datklima to niezależny arbiter techniczny — dane i ich źródła, bez cen i sprzedaży.